Hytronik Electronics HC418VRF Lighting Control Switch User Manual of HC418V RF HC424RF

Hytronik Electronics Co., Ltd Lighting Control Switch of HC418V RF HC424RF

User Manual

120~277VAC 60Hz.Model NO.:HC418V/RF Model NO.:HC424RFRF antennaRotary coding switchStand-by periodStand-by dimming levelDetection areaDaylight thresholdStand-by periodStand-by dimming levelHold-timeRotary coding switchRF AntennaLED indicationDaylight sensorBlock A6, Nan’pu Science & Technology Park, Hao’si, Shajing Street, Bao’an District, Shenzhen, P.R.C. 518104T: 86 755 27322200                 F: 86 755 27308687 E: info@hytronik.com            W: www.hytronik.com HYTRONIK  ELECTRONICS CO.,LTD2.2 Keep the RF antenna at least 3cm away from the driver or ballast.1.42.1 Ensure that the electricity supply is switched off completely before installing or servicing this product.PROTECTION LEVELSTANDBY PERIODSTANDBY DIMMING LEVELWORKING TEMPERATUREHC418V/RFUp to 30 meters indoor transmission and 100 meters in open area.Fixed address coding with 10 channels (max. 10 groups)Diameter Max. 12m5s~30min-20 ~ +60℃0s, 10s~1h, + 0s, 10s~1h, +10~50% 10~50%-20 ~ +60℃Max. 6m Max. 6mHC424RF120~277VAC  60Hz 120~277VAC  60Hz200W@120VAC; 500W@277VAC(capatitive Load)
Wring with any 1~10V control gear to achieve dimming function.HC418V/RFLED Driver LED DriverHC424RFRF wireless communication makes installation easier with no cables connection.The motion at 1 sensor (the master unit) can be passed onto other pre-defined individuals (the slave units) through RF transmission. This wireless radio wave transmission can reach 100 meters in open area with internal RF antenna, 30 meters blocked by one wall, 20 meters blocked by two walls.Settings for HC418V/RFI –  5SII – 30SIII – 1 minuteIV – 5 minutesV – 10 minutesVI – 20 minutesVII – 30 minutesI –  DisableII –  50 luxIII – 10 luxIV – 2 luxI – maximum range up to 100%II – 75% III – 50%IV – 10%  I –  0SII – 10SIII – 1 minuteIV – 5 minutesV – 10 minutesVI – 30 minutesVII – 1 hourVIII – +Note: “0s” means on/off control; “+∞” means 2 steps of dimming control, fixture never switch off.∞ +∞ This is the time period you would like to keep at the  low light output level before it is completely switched off in the long absence of people. Stand-by period (corridor function)I –  10%II –  20%III – 30%IV – 50%This is the dimmed low light output level you would like to have after the hold-time in the absence of people. Stand-by dimming level100%75%50%10%1     2 IIIIIIIVIIIIIIIVVVIVII1    2   35S30S1min5min10min20min30minI II IIIIVDisable50 lux10 lux2 lux1      2  0S10S1min 5min 10min 30min 1hI IIIIIIVVVIVIIVIII1    2   310%20%30%50%I  II III IV 1      2   This determines the time the fitting remains at 100% level on motion detection and is set sith DIP swiches at the sensoritself, refer to figure. The walk test seing is useful when installing the fitting to establish correct operation and range.The following settings are available:Hold time:Daylight sensor:This setting holds off the 100% light output should there sufficient daylight andis set using DIP switches at the sensor, referto figure. The following settings are available: Detection Area:This determines the effective range of the motion detector and is set by DIP switches at the sensor itself, refer to figure.Note that reducing the sensitivity will also narrow the detection range.The following settings are available:*In disable mode the lamp(s) will always be on with motion detected and operate at 100% light output, even in bright daylight.
I –  10%II –  20%III – 30%IV – 50%Settings for HC424RF Stand-by period (corridor function)This is the time period you would like to keep at the  low light output level before it is completely switched off in the long absence of people. I –  0SII – 10SIII – 1 minuteIV – 5 minutesV – 10 minutesVI– 30 minutesVII– 1 hourVIII– +∞+∞0S10S1min 5min 10min 30min 1hI IIIIIIVVVIVIIVIII1     2    3Stand-by dimming levelThis is the dimmed low light output level you would like to have after the hold-time in the absence of people. 10%20%30%50%I  II III IV 1     2   RF grouping (max. 10 channels)Using  a screwdriver to adjust the rotary switch on both the master & slave unit, to keep them pointing at the same channel, the grouping is then automatically completed. 10 channels (max. 10 groups) available for both the master & slave unit.  Using a screwdriver to point the arrow to the same position on the master unit and slave units.   masterslaveSECTION 4 RF GROUPINGSECTION 5 FUNCTIONS5.1 100H burn-in mode for fluorescent lampWith simple operation, rapidly turn off/on the fixture 3 cycles wihin 3 sec. (the green LED on the sensor flashes and the fixture blinks 3 times to indicate the success of setup), lamp will be 100% on for 100 hours, and then automatically goes to sensor modeafter 100 hours. This is crucial to secure the lifetime of fluorescent lamp, when new fixture is installed,or old lamp is replaced.This 100h burn-in feature can be cancelled by turn off/on the fixture 1 cycle within 1 sec.With simple operation, rapidly turn off/on the fixture 2 cycles within 2 sec:a. the green LED on the sensor flashes slowly for 5 seconds, meanwhile the fixture blinks twice.b. the daylight sensor measures and remembers the surrounding lux for 1 sec.c. the fixture and green LED is on for 10s to indicate the success of learning.5.2 Ambient daylight thresholdThis feature enables the fixture to function well in any real application circumstance, where the daylight penetratedinto fixture may vary a lot.The latest surrounding lux value overwrites previous lux value learned. Both the setting on DIP switch and the learned ambient lux threshold can overwrite each other.The latest action stays in validity. * * * Note: “0s” means on/off control; “+∞” means 2 steps of dimming control, fixture never switch off.
Designed in the software, the sensor switches on/off the load right on the zero-cross point, to ensure the min. current passing throughthe relay contact point, and enable the max. load and life-time of the relay.5.3 Zero-cross relay operationDouble L N terminal makes it easy for wire loop-in and loop-out, saves the cost of terminal block and assembly time.  5.4 Loop-in and loop-out1-10v output on the master unit  HC418V / RF is isolated, SELV output; while the 1-10v on the slave unit  HC424RF is     non-isolated.Motion sensor overwrites daylight sensor, meanning the daylight sensor starts to check the ambient natural light only when the     lamp is switch off (motion hold-time ellapsed).  * * SECTION 6 TROUBLE SHOOTING YDEMER ESUAC YDEMER ESUAC NOITCNUFLAMThe load will not work  gnittes tsujdA detceles gnittes lortnoc-thgil tcerrocnI daol ecalpeR ytluaf daoL NO hctiwS FFO hctiws sniaM gnittes enoz kcehC enoz noitceted eht ni tnemevom suounitnoC no syawla si daol ehTThe load is on without any identifiable  movement The sensor is not mounted for reliably detecting movement  Securely mount enclosure Movement occurred, but not identified by the sensor  (movement behind wall, movement of small object in  immediate lamp vicinity etc.) Check zone setting  The load will not work despite movement  Rapid movements are being suppressed to minimize  malfunctioning or the detection radius is too small  Check zone setting FCC NOTE:This device complies with Part 15 of the FCC Rules.Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.THE MANUFACTURER IS NOT RESPONSIBLE FOR ANY RADIO OR TV INTERFERENCE CAUSED BY UNAUTHORIZED MODIFICATIONS OR CHANGE TO THIS EQUIPMENT. SUCH MODIFICATIONS OR CHANGE COULD VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.

Navigation menu